COLD PLATES

Data center cooling

NVIDIA GB200

  • 2700W

  •  Δp = 2 kPa GPU + 3.1kPa Grace CPU

  • B200 θ = 0.0193, CPU θ = 0.0161 [2L/min]

Verification preformed under the following conditions:

PG25 coolant at 20 degrees °C inlet, 1 liter per minute flowrate for each B200 and 2 liter per minute for Grace CPU. Fitting pressure drop excluded

SEND INQUIRY

NVIDIA B200

  • 1200W

  •  Δp = 2 kPa

  • θ = 0.0193K/W

Verification preformed under the following conditions:

PG25 coolant at 20 degrees °C inlet, 1 liter per minute flowrate. fitting pressure drop excluded

SEND INQUIRY

AMD SP7

  • 600W

  • Δp = 1.6 kPa

  • θ = 0.0186K/W

Verification preformed under the following conditions:

PG25 coolant at 20 degrees °C inlet, 1 liter per minute flowrate. fitting pressure drop excluded

SEND INQUIRY

AMD MI355X

  • 1400W

  • Δp = 2.1 kPa

  • θ = 0.0196K/W

Verification preformed under the following conditions:

PG25 coolant at 20 degrees °C inlet, 1 liter per minute flowrate. fitting pressure drop excluded

SEND INQUIRY

AMD SP5

  • 500W

  • Δp = 1.8 kPa

  • θ = 0.0186K/W

Verification preformed under the following conditions:

PG25 coolant at 20 degrees °C inlet, 1 liter per minute flowrate. fitting pressure drop excluded

SEND INQUIRY

Other data center products

RACK MANIFOLDS

ZeroKelvin rack manifolds feature optimized geometries for perfectly balanced flow distribution across every outlet. Designed with precise cross-sections and tested up to 100 bar, they deliver reliable performance for demanding cooling environments.

END-TO-END COOLING SOLUTION

ZeroKelvin, together with partners offers a complete end-to-end cooling solution that integrates chillers or dry coolers, rear-door heat exchangers, rack manifolds, and plumbing into one unified system. This holistic approach delivers higher efficiency, built-in redundancy, and simplified deployment with a single vendor and a single point of responsibility.